Refrigerant type is the fastest way to sort a mechanical fleet into what must be replaced and what can be planned. It is printed on every data plate, and it maps directly onto federal rules that are already in effect.
R-22: the item that cannot wait
R-22 was permanently banned from production and import in the United States effective January 1, 2020. It is now available only from reclaimed and stockpiled supply, at substantially elevated prices, and any system still running on it faces increasingly difficult and expensive service.
Concentrations can be large. At one property we assessed, 71 residential condensing units were confirmed R-22 from a single installation cycle. On an 810-unit community, roughly 175 systems were still on R-22. In both cases our recommendation was the same: replace all of it, and in the larger portfolio, do it in Year 0.
R-410A: plannable capital
R-410A is being phased down under the AIM Act and the EPA Technology Transitions Rule. Since January 1, 2025, the EPA has prohibited the manufacture and import of new residential and light commercial air-conditioning equipment using refrigerants with a global warming potential above 700. R-410A has a GWP of 2,088, so new R-410A equipment production has ended.
Existing R-410A equipment, however, remains fully serviceable for years. The practical takeaway for an owner is that an R-410A fleet does not need to be replaced on an emergency basis. It is normal, plannable capital.
| Refrigerant | GWP | Status | What to do |
|---|---|---|---|
| R-22 | 1,810 | Production and import banned since 2020 | Replace. Prioritize in Year 0. |
| R-410A | 2,088 | New equipment production ended; serviceable | Replace on a steady annual schedule. |
| R-454B | 466 | Compliant A2L replacement | Specify for new chillers and systems. |
| R-32 | 675 | Compliant A2L replacement | Specify for new residential systems. |
What changes with A2L equipment
R-32 and R-454B are classified A2L, meaning mildly flammable. That brings updated installation requirements, and it means a like-for-like swap is not always like-for-like: line sets, clearances and in some cases leak detection need to be reviewed. Build that into the unit price rather than discovering it on the first install.
How to carry it in the model
- Count the R-22 systems and carry their replacement as near-term capital.
- Run the R-410A fleet as an annual capital line sized to the age distribution, not as a one-time event.
- Require certified EPA Section 608 recovery and documentation on every removal. It is a compliance requirement and a clean record for the file.
- Ask for the refrigerant split in every diligence report. If it is not there, the report is not finished.
Written by the Air Force Mechanical team from field assessments and active programs.
General guidance only. Confirm code and regulatory requirements for your property.