Once the R-22 equipment is dealt with, the remaining question on most multifamily fleets is how fast to replace the mid-life R-410A systems. The answer matters twice: once for the hold-period budget, and again at disposition, when a buyer decides whether the remaining fleet is ordinary capital or a problem.
Start with natural turnover
A residential split system lasts roughly twelve to eighteen years. An 810-unit portfolio therefore turns over about forty-five to seventy systems a year simply to hold its average age steady. Any replacement pace below that range means the fleet is getting older every year.
Why 75 was the midpoint
On that portfolio, with about 615 R-410A systems at an estimated average age near ten years, we set 75 systems a year as the planning midpoint inside a reasonable band of 50 to 100. At 75 a year the program stays comfortably within the natural rhythm of the fleet. After three years roughly 390 R-410A systems remain, all of them serviceable.
| Pace | What it means | How it reads at exit |
|---|---|---|
| 50 a year | Roughly holds average age | Defensible if the fleet is young; lighter annual capital |
| 75 a year | Gradually lowers average age | Recurring capital a future owner simply continues |
| 100 a year | Actively renews the fleet | Strongest fleet at sale; heaviest annual spend |
Run it as a line, not an event
The framing matters as much as the number. A one-time replacement event looks like catch-up spending on deferred maintenance. A steady annual capital line looks like what it is: ordinary recurring capital. Framed that way, the spend reads as a program the next owner continues rather than a liability they inherit.
Bundle the work that rides along
Each swap is a mobilization, and several scopes are far cheaper inside one than outside it. On the same portfolio every swapped system received a new raised return plenum and a thermostat, and the line set was addressed at the same visit. The systems that were not being swapped received a one-time condenser cleaning, hurricane tie-downs, line-set insulation and secured low-voltage wiring.
What can move the number
- Line sets. Whether existing line sets can be reused is the variable most likely to move a split-system program.
- Ductwork strategy. Cleaning, repair or replacement each carry very different costs.
- Electrical capacity. Confirm it before equipment is ordered.
- The sample. A 10 to 15% data-plate census turns the pace from a judgment into a calculation.
Written by the Air Force Mechanical team from field assessments and active programs.
General guidance only. Confirm code and regulatory requirements for your property.